Study Investigates Solar District Cooling Potential for Saudi Arabia

2018.11.19     From: solarpaces.org


Instead of running air conditioners on fossil-fueled electricity, University of Bergamo researchers Guiseppe Franchini and Antonio Perdichizzi propose an alternative cooling technology; using a thermal form of solar energy to provide solar district cooling in the Saudi Kingdom.


Their study of the economics of solar district cooling was published at Energy Conversion and Management, in Performance prediction of a solar district cooling system in Riyadh, Saudi Arabia – a case study.


"Our proposed solution is a solar district cooling system for new settlements in Saudi Arabia. This concept combines solar cooling and district cooling," said Franchini.


The study has implications for the climate. With one of the world's highest per capita energy consumption rates, cooling accounts for more than 70% of electricity use in Saudi Arabia's year round hot climate. But the Kingdom still produces this electricity almost entirely using fossil fuels, despite its abundant solar resource.


Wider application in the world's hotter future


Using solar heat for district cooling has seen increased interest as the need for cooling is expected to grow as the climate heats up, not only in Saudi Arabia, but in many regions.


"Climate change is a good challenge because of the increase of the cooling load expected due to increasing temperatures," Franchini added.


"So this technology could be interesting also for other locations like in the Mediterranean. In Italy for example, cooling loads are increasing more and more with the higher temperatures in the summer. So this technology can have a good application also in other countries."


Early in their investigation, Perdichizzi and Franchini determined that solutions based only on PV exhibit some weakness points: the main critical issue is related to the electric storage by batteries for large size systems. So their focus became solar thermal technologies. But which technology would be best?


"Our investigation was comparing solar district cooling from parabolic trough collectors or solar cooling from evacuated tube collectors,"said Perdichizzi.


"One is based on single stage absorption chiller driven by evacuated tube collectors operating at medium temperatures. The second one is based on two stage absorption chillers driven by parabolic troughs operating at a higher temperature around 170°C."



Parabolic troughs beat “rooftop” solar thermal


Since an absorption chiller does not require very high temperatures for cooling (about 170°C for double-stage and 100°C for single-stage), the obvious choice would seem to be the typical solar thermal rooftop collectors, such as is popularly used to heat swimming pools or to make hot water in homes at comparatively low temperatures.


Yet after comparing the two, they found that a parabolic trough solar field would be the most economical.


In this case the solar collectors would not be connected to a power block, as they would be for generating electricity (normally at about 400°C in trough CSP). Instead, the curved mirrors would simply be used to concentrate solar energy in order to heat water to just 170°C.


The study assumed a proposed district of 100 buildings, with each structure housing up to ten people.


Using parabolic trough collectors, the solar field needed would occupy about 9,000 sq meters: a bit larger than a football field. But a lot more space would be needed, about 15,000 sq meters, to supply the needed thermal energy from evacuated tube "rooftop" solar collectors.


Relatively low temperature need


The solar field would supply a two-stage absorption chiller, at less than half the temperature produced by trough CSP for generating electricity in a power block.


"The two-stage absorption chiller is driven by hot water at just 170°C and produces chilled water at 5 or 7°C which is used for district cooling," explained Franchini.


"Two-stage absorption chillers can be driven by different sources; by steam, or by pressurized water. In our case we suppose that it is driven by pressurized liquid water and heated by the parabolic trough so our scheme is based on the field of parabolic troughs producing a pressurized hot water temperature of 170° Celsius."


Most cost-effective way to cover a very brief peak load?


The researchers chose not to cover 100% of the annual cooling need, because the peak load, 4-5 MW, is typically only for a week in summer. An auxiliary electric chiller would cover that brief peak.


"Typically a solar fraction of 100% is too high because it means oversizing the solar field – yet the absorption chiller would only be used for a few hours per year. So the design is for a cooling solar fraction of about 80%," Perdichizzi explained.


"The remaining 20% would be covered by an auxiliary conventional chiller using electricity."


The insulated pipelines of 12,000 meters throughout the district constitutes cold storage in a sense, with a temperature loss of just 1-2 degrees overnight.


Wider applications for solar district cooling


The researchers say solar district cooling could be either designed into a new district from scratch or retrofitted to existing districts, and district cooling could be applied at different scales.


"This technology could be applied at different sizes. For different communities whether small, medium, or large. Of course all this equipment should be scaled up increasing the size," said Perdichizzi.


"What we analyzed was a compound of perhaps 100 just because that's a very common size for new compounds being built in Saudi Arabia."


They modeled two possible sites, on the coast at Jeddah, and inland at Riyadh. Although initially appealing (a source of water), Jeddah proved less suitable, due to the detrimental effect of the high humidity levels close to the sea, which reduced the available solar resource.


Comprehensive district cooling plan would include building efficiency


They used models to predict the performance of the system, by the hour, throughout all of the year, to calculate the exact saving of energy and fossil fuel and carbon dioxide, to cost and demonstrate the technical feasibility of the entire system, in partnership with King Abdullah City for Atomic and Renewable Energy (K.A.KARE).


"After the cooling load calculation we designed a pipe network from the cooling station to the buildings," said Perdichizzi. 

"You need to know how much is the energy for delivering water in the pipes, their diameter, their insulation. And finally we are able to carry out simulations of the solar field and the absorption chiller, and the integration of the two under real meteorological data. A full optimization of the system is what is new."


What makes their study unique is that their first aim was to optimize the energy consumption of the villas served within the district to create a comprehensive district cooling plan.


To this end, the two researchers leverage their previous experience in architectural energy efficiency, as the designers of the first Passive Haus in Dubai, which is a fully autonomous net zero design of a 700 square meter building; tapping into that related expertise in investigating district solar cooling.


Leave your thoughts here

Reports(Member Only)

See more+
  • CSP Focus Membership Proposals

    We are now proposing CSP Focus Membership, hoping to better serve our members to keep pace with the latest updates of ongoing CSP projects worldwide, and to establish and maintain business relations with major shareholders of the projects. CSP Focus offers to Membership exclusive access to:1. Daily/Weekly update and analysis on CSP policies, projects, technologies, market trend and corporate relea

  • The Latest CSP Focus Monthly Update

    Join CSP Focus Membership to Get the Latest CSP Focus Monthly Update December Edition.

  • CSP Project Monthly Update 2022 December Edition

    CSP Focus is presenting CSP Project (China) Update 2022 December Edition.Detail report is available for CSP Focus Membership.

  • Presentations-CSP Focus China 2021

    The Report is for CSP Focus Members only.

Upcoming Events

See more+

Project Updates

See more+

CONTACT US

Tex:

Email:csp@cspfocus.cn


备案/许可证编号为:沪ICP备17051021号

Wechat public platform

Follow CSP Focus for more news